Click to Enlarge Image

100A TP MCCB in MCENC1 Enclosure

Product Code

MCE100T
  • Range has four frames available
  • Available in ratings from 63-800A
  • Interrupting capacities up to 36kA at 400/415V AC
  • Standard calibration is at 40 degrees
  • Current limiting design

General Characteristics

Current Rating

100A

Depth

170mm

Height

400mm

Width

300mm

Incoming Terminal Capacity

Tunnel Terminal 120mm Square Cable

Packaging Types

Each

Product Range

MC Range

Standards

BS EN 60947-2

Rated Magnetic Operation

10 x In

Rated Thermal Adjustment

0.8 - 1 x In

Utilisation Category

A

ZS Values 0.4 Second

0.22 ohm

ZS Values 5 Second

0.3 ohm

Equipment Type

Fixed Stationary

Enclosure

MCENC1

Fault Current Rating

36 kA

Frequency

50HZ

Breaking Capacity

36 kA

Rated Operating Voltage

230/400V ac.

Protection Class IP Rating

IP3X

Operating Ambient Temperature

-5 to +35 C

Terminal Tightening Torque

Tunnel Terminal - 6Nm MAX - 120mm2

Mechanical Life

>15000

Electrical Life

>5000

Short Circuit Making Capacity

36 kA

Number Of Poles

Triple Pole with bolted neutral link