Click to Enlarge Image

200A TP MCCB in MCENC2 Enclosure

Product Code

MCE200T
  • Range has four frames available
  • Available in ratings from 63-800A
  • Interrupting capacities up to 36kA at 400/415V AC
  • Standard calibration is at 40 degrees
  • Current limiting design

General Characteristics

Current Rating

200A

Depth

170mm

Height

700mm

Width

300mm

Packaging Types

Each

Product Range

MC Range

Standards

BS EN 60947-2

Rated Magnetic Operation

5 - 10 x In

Rated Thermal Adjustment

0.8 - 1 x In

Utilisation Category

A

ZS Values 0.4 Second

0.11 ohm

ZS Values 5 Second

0.13 ohm

Enclosure

MCENC2

Fault Current Rating

36kA

Rated Operating Voltage

230/400V ac.

Protection Class IP Rating

IP3X

Operating Ambient Temperature

-5 to +35 C

Terminal Tightening Torque

Tunnel Terminal - 6Nm MAX - 120mm2

Short Circuit Making Capacity

36kA

Number Of Poles

Triple Pole with bolted neutral link