15 Way 125A Triple Pole and Neutral XL Range MCB Distribution Board Complete with 125A Triple Pole Switch Disconnector Incomer And Type 2 Surge Protection Device
- Proteus Switchgear offers a comprehensive range of Lightning and Surge Protection Devices for single and three phase applications
- Whether it?s a stand-alone device or a pre-assembled SPD in a distribution board, Proteus can provide a coordinated system to meet your specific requirements
Datasheet & Declaration Download
- Additional information
Additional information
| Height | 842 mm |
|---|---|
| Width | 600 mm |
| Depth | 132 mm |
| Weight | 21 Kg |
| Short Circuit Rating | 10kA Icc. |
| Torque | Isolator 2-2.5 Nm, M8 and M10 Bolt 20Nm max. |
| Ambient Temperature | -5 to +40 C |
| Mounting | Wall Mounted |
| Guarantee | 12 Months |
| Frequency | 50 Hz |
| Cable Entry | Top And Bottom Glandplates Removable For Ease Of Cutting |
| Current Rating | 125A |
| Rated Operated Voltage | 230/400V ac. |
| Number of Ways | 15 Way |
| Incoming Terminal Capacity | Neutral M10 Bolt and Earth M8 Bolt, Tunnel Terminal 50mm Square Cable |
| Number of Outgoing Ways | 15 Way |
| Standards | BS EN 61439 pt 1&3 |
| Protection Class IP Rating | IP3X |
| Enclosure | 1.2mm Cold rolled steel with an epoxy paint finish to RAL7035 matt grey. |
| Door Covers | Screw fixed internal cover. Side hinged overall door (removable) complete with steel turn catch. |
| Switchgear Fitted | Triple Pole Switch Disconnector Incomer 125A Type 2 Surge Protection Device |
| Compliance | Electromagnetic Compatibility Directive 2014/30/EU, Low Voltage Directive 2014/35/EU, Restriction of the use of certain hazardous substances directive 2011/65/EU, Waste Electrical and Electronic Equipment directive 2012/19/EU |
| Intended Purpose |