200A Four Pole Incoming Kit XL Split Meter Boards

  • Each individual XL distribution board unit with meter fitted must not exceed 100A full load current per phase; Select isolator incoming kit to satisfy the total load current demand;
Download PDF
Datasheet & Declaration Download

Additional information

Height

400 mm

Width

600 mm

Depth

132 mm

Short Circuit Rating

10kA Icc.

Torque

Isolator M8 Bolt 20Nm max, M10 Bolt 20Nm max.

Ambient Temperature

-5 to +40 C

Number of Poles

Triple Pole And Neutral

Mounting

Wall Mounted

Guarantee

12 Months

Frequency

50 Hz

Cable Entry

Bottom Glandplates Removable For Ease Of Cutting. Bottom Glandplate Also With Variable Knockout 25mm and 33mm

Current Rating

200A

Rated Operated Voltage

230/400V ac.

Incoming Terminal Capacity

M8 Bolts 95mm Square Cable and Earth M10 Bolt

Packaging Types

Each

Standards

BS EN 61439 pt 1&2

Protection Class IP Rating

IP3X

Enclosure

1.2mm Cold rolled steel with an epoxy paint finish to RAL7035 matt grey.

Door Covers

Screw fixed cover.

Switchgear Fitted

Four Pole Switch Disconnector Incomer 200A

Compliance

Low Voltage Directive 2014/35/EU, Restriction of the use of certain hazardous substances directive 2011/65/EU, Waste Electrical and Electronic Equipment directive 2012/19/EU

Intended Use

200A incoming section for XL split load, metered MCB boards.

Product Range

XL Range