250A Triple Pole Switch Disconnector
- This range offers ratings from 200A up to 250A
- The operating dolly is capable of being locked in either the ON or OFF position
- When locked in ON position it will no longer function as an Switch Disconnector
- Positive indication of the contacts only occurs when dolly is in the OFF position
- Terminals are tunnel design and offer generous cable capacity of 50mm? for solid stranded conductors
- Busbar connectivity – thickness 3mm max
- Additional information
Additional information
| Height | 185 mm |
|---|---|
| Width | 106 mm |
| Depth | 61.5 mm |
| Weight | 0.9 Kg |
| Torque | 20 Nm |
| Mounting | Din Rail |
| Guarantee | 12 Months |
| Frequency | 50 Hz |
| Current Rating | 25A |
| Cable Clamp | Square Cage Clamp |
| Rated Operated Voltage | 230/400V ac. |
| Incoming Terminal Capacity | M8 Bolts 95mm Square Cable |
| Terminal Type | Cage Clamp |
| Packaging Types | Each |
| Standards | BS EN 60947-3 |
| Protection Class IP Rating | IP2X |
| Compliance | Low Voltage Directive 2014/35/EU, Restriction of the use of certain hazardous substances directive 2011/65/EU, Waste Electrical and Electronic Equipment directive 2012/19/EU |
| Intended Purpose | 250A AC22B 3 pole switch disconnector. For switching LV loads. Used in distribution panels |