400A 4 pole horizontal busbar chamber in steel enclosure. Each chamber is supplied with one initial set of 4 connection bolts. Chamber width 1803mm.

  • Manufactured to BSEN 61439-1 & 2
  • Twin bar design 4 pole configuration
  • No drilling of the busbar necessary
  • 6 ratings from 100A to 800A
  • 36kA short circuit fault level
  • Fully rated neutral
  • Set of 4 clamps supplied with each chamber

PDF Download

Datasheet Download

Download PDF
Declaration Download

Additional information

Height

400 mm

Width

1803 mm

Depth

190 mm

Rated Insulation Voltage

690V

Weight

45.3 Kg

Short Circuit Rating

36kA Icc. Remote MCCB or BS88 fuse protection

Torque

M10 – 40Nm (BLC10/48)

Ambient Temperature

-5 to +40 C

Mounting

Wall Mounted

Guarantee

12 Months

Frequency

50 Hz

Current Rating

400A

Rated Operated Voltage

230/400V ac.

Packaging Types

Each

Product Range

Busbar Chamber

Standards

BS EN 61439-1

Protection Class IP Rating

IP3X

Enclosure

1.6mm mild steel. Screw on end plates. Plain top, bottom and sides. Drill to suit site requirements. Bolt on front cover, Pozi screw.

Door Covers

Screw fixed covers.

Switchgear Fitted

Four connection bolts fitted for incoming cable (One per bar). BLC10/48

Finish

RAL 7035. Powder coated. electrostatically applied.

Compliance

Low Voltage Directive 2014/35/EU, Restriction of the use of certain hazardous substances directive 2011/65/EU, Waste Electrical and Electronic Equipment directive 2012/19/EU

Intended Purpose

Busbar chambers form the distribution means between various items of switchgear selected and fitted by an electrical contractor or engineer

Pollution Degree

3

EMC Environment

Type A

Maximum Altitude

2000m

Dielectric Strength

2000V ac