400A Four Pole 50kA Moulded Case Circuit Breaker
- MC Range 4P MCCB’S available from 63A to 800A
- Single, Triple and Four pole available, Single and Triple pole may be fitted as outgoing devices in MC range panel boards
- Interrupting capacities up to 50kA at 400/415V AC
- Standard calibration is at 40 degrees
- Current limiting design
- Additional information
- Product Instructions
Additional information
| Height | 347 mm |
|---|---|
| Width | 188 mm |
| Depth | 158 mm |
| Rated Insulation Voltage | 690V |
| Weight | 8.5 Kg |
| Short Circuit Rating | 16kA at 690V, 42kA at 500V, 50kA at 415V, 50kA at 440V |
| Mechanical Life | >15000 |
| Electrical Life | >6000 |
| Terminal Cable Capacity | Lugged (M12) |
| Torque | 56 Nm |
| Ambient Temperature | -20 to +60 C |
| Guarantee | 12 Months |
| Frequency | 50 Hz |
| Current Rating | 400A |
| Rated Operated Voltage | 400V ac. |
| Incoming Terminal Capacity | Lug connection. M12 bolt |
| Packaging Types | Each |
| Product Range | Moulded Case Circuit Breaker |
| Standards | EN/IEC 60947-2 |
| Protection Class IP Rating | IP2X |
| Rated Magnetic Operation | 5 – 10 x In |
| Rated Thermal Adjustment | 0.8 – 1 x In |
| Enclosure | ABS |
| Compliance | Low Voltage Directive 2014/35/EU, Restriction of the use of certain hazardous substances directive 2011/65/EU, Waste Electrical and Electronic Equipment directive 2012/19/EU |
| Intended Use | MCCB?s are designed to automatically disconnect the supply in the event of a circuit overload. |
| Bi-directional | Yes |
| Impulse Withstand Voltage | 8kV |
| Trip Unit Type | Thermal-magnetic |
| Utilization Category | A |
| Pollution Degree | 3 |