50A Single Pole 36kA Moulded Case Circuit Breaker
- MC Range MCCB’S available from 16A to 250A (200A single pole)
- Single, Triple and Four pole available, Single and Triple pole may be fitted as outgoing devices in MC range panel boards
- Interrupting capacities up to 36kA at 400/415V AC
- Standard calibration is at 40 degrees
- Current limiting design
- Enclosures available for mounting individually (250A use larger frame size MC250TLF)
- Additional information
- Product Instructions
Additional information
| Height | 158 mm |
|---|---|
| Width | 35 mm |
| Depth | 109 mm |
| Rated Insulation Voltage | 690V |
| Weight | 0.7 Kg |
| Short Circuit Rating | 15kA at 83V DC, 36kA at 240V AC |
| Mechanical Life | >20000 |
| Electrical Life | >8000 |
| Terminal Cable Capacity | <120mm2 (box clamps) |
| Torque | 8 Nm |
| Ambient Temperature | -20 to +60 C |
| Guarantee | 12 Months |
| Frequency | 50 Hz |
| Current Rating | 50A |
| Rated Operated Voltage | 230V ac. |
| Incoming Terminal Capacity | Tunnel Terminal 120mm Square Cable |
| Product Range | Moulded Case Circuit Breaker |
| Standards | EN/IEC 60947-3 |
| Protection Class IP Rating | IP2X |
| Rated Magnetic Operation | 500A |
| Rated Thermal Adjustment | Fixed |
| Enclosure | BMC |
| Compliance | Low Voltage Directive 2014/35/EU, Restriction of the use of certain hazardous substances directive 2011/65/EU, Waste Electrical and Electronic Equipment directive 2012/19/EU |
| Intended Use | MCCB?s are designed to automatically disconnect the supply in the event of a circuit overload. |
| Bi-directional | Yes |
| Impulse Withstand Voltage | 8kV |
| Trip Unit Type | Thermal-magnetic |
| Utilization Category | A |
| Pollution Degree | 3 |













