630A Triple Pole and Neutral Enclosed MCCB Complete with Adustable Earth Leakage Unit
- Available in ratings from 100-630A, 3 or 4 pole versions
- Interrupting capacities up to 36kA at 400/415V AC
- Current limiting design
- CT internal diameters of 70mm from 100A to 200A and 120mm for current ratings from 250A to 630A
- Additional information
- Datasheet
Additional information
Height | 950 mm |
---|---|
Width | 400 mm |
Depth | 170 mm |
Weight | 28.16 Kg |
Short Circuit Rating | 36 kA |
Torque | M10 Bolt 40Nm max., M12 Bolt 50Nm max |
Ambient Temperature | -5 to +40 C |
Number of Poles | Triple Pole And Neutral |
Mounting | Wall Mounted |
Guarantee | 12 Months |
Frequency | 50 Hz |
Cable Entry | Top And Bottom Endplates Removable For Ease Of Cutting |
Current Rating | 630A |
Rated Operated Voltage | 230/400V ac. |
Incoming Terminal Capacity | M12 Bolts 240mm Square Cable and Earth M10 Bolt |
Packaging Types | Each |
Standards | BS EN 60755, BS EN 61439 pt 1&2, BS EN 61543, BS EN 62020 |
Protection Class IP Rating | IP3X |
Rated Magnetic Operation | 4 – 8 x In |
Rated Thermal Adjustment | 0.8 – 1 x In |
Enclosure | 1.6mm Cold rolled steel with an epoxy paint finish to RAL7035 matt grey. |
Door Covers | Screw fixed covers. |
Switchgear Fitted | TP Mccb 630A Adjustable Earth Leakage Relay |
Compliance | Electromagnetic Compatibility Directive 2014/30/EU, Low Voltage Directive 2014/35/EU, Restriction of the use of certain hazardous substances directive 2011/65/EU, Waste Electrical and Electronic Equipment directive 2012/19/EU |
Intended Use | MCCB?s are designed to automatically disconnect the supply in the event of a circuit overload. |
Product Range | Moulded Case Circuit Breaker with Earth Leakage relay |