Proteus 400A Four Pole 36kA Enclosed MCCB complete with Adjustable Type B Earth Leakage Unit

  • Available in ratings from 63-630A
  • Bidirectional
  • Interrupting capacities up to 50kA at 400/415V AC
  • Current limiting design
  • CT internal diameters of 90mm

PDF Download

Datasheet Download

Download PDF
Declaration Download

Additional information

Height

950 mm

Width

400 mm

Depth

170 mm

Weight

14 Kg

Short Circuit Rating

36kA

Torque

M12 Bolt 50Nm max.

Ambient Temperature

-5 to +40 C

Mounting

Wall Mounted

Guarantee

12 Months

Frequency

50 Hz

Cable Entry

Top And Bottom Endplates Removable For Ease Of Cutting

Current Rating

400A

Rated Operated Voltage

230/400V ac.

Incoming Terminal Capacity

M12 Bolts 240mm Square Cable and Earth M10 Bolt

Packaging Types

Each

Product Range

Enclosed Earth Leakage Device

Standards

BS EN 60947 pt 1&2, BS EN 61010-1, BS EN 62423

Protection Class IP Rating

IP3X

Rated Magnetic Operation

5 – 10 x In

Rated Thermal Adjustment

Adjustable

Enclosure

1.6mm Cold rolled steel with an epoxy paint finish to RAL7035 matt grey.

Door Covers

Screw fixed covers.

Switchgear Fitted

4P Mccb 400A and Adjustable Type B Earth Leakage Relay

Compliance

Electromagnetic Compatibility Directive 2014/30/EU, Low Voltage Directive 2014/35/EU, Restriction of the use of certain hazardous substances directive 2011/65/EU, Waste Electrical and Electronic Equipment directive 2012/19/EU

Intended Purpose

MCCBs are designed to automatically disconnect the supply in the event of a circuit overload or earth leakage

Bi-directional

Yes

Electrical Life

>3000

Mechanical Life

>15000